Shopping security
The HIMA F9404 is a 4-channel Safety Relay Output Module designed for the HIMA Planar4 safety system, engineered for high-current switching in SIL 4 safety loops. Unlike the logic-processing modules like the F3313 and F3225, the F9404 acts as the final control element, physically interfacing with the field to control high-power equipment like solenoid valves, motor starters, or alarm horns.
Using electromagnetic relays, the F9404 provides potential-free (dry) contacts, allowing it to switch external voltages such as 230 VAC or 120 VDC. It operates with a de-energize to trip logic, ensuring that a power loss or fault state safely shuts down the field devices.
Potential-Free Contacts:
Switches external voltages (e.g., 230 VAC or 120 VDC) while maintaining complete isolation from the 24 VDC logic system.
Redundant Internal Design:
Features safety-oriented relay circuits, ensuring that a single component failure does not prevent a safety shutdown, achieving fail-safe operation.
High Switching Capacity:
Capable of switching loads up to 4 Amperes, making it more robust than standard electronic output modules.
Positive Safety Logic:
Operates on a de-energize to trip principle, where an open circuit equals a safe or trip state, ensuring that the system defaults to a safe condition during faults.
| Parameter | Specification Details |
|---|---|
| Number of Channels | 4 Relay Outputs |
| Contact Type | 1 NO (Normally Open) / 1 NC (Normally Closed) per channel |
| Max Switching Voltage | 250 VAC / 120 VDC |
| Max Switching Current | 4 A (at 24 VDC / 230 VAC) |
| Min Switching Load | 10 mA / 12 V |
| Response Time | Approx. 10 ms to 15 ms |
| Safety Integrity | Up to SIL 4 (Planar4 standard) |
| Power Consumption | 24 VDC: approx. 140 mA |
| Space Requirement | 4 Units (Standard HIMA rack width) |
The F9404 serves as the interface between the safety logic system and field devices, enabling the physical switching of high-power equipment. Here's how the logic chain typically works:
Input: A signal from a sensor (e.g., a pressure switch) enters the system through the F3313 Filter Module, where it is conditioned.
Decision: The F3225 AND Gate Module processes the signal and determines whether the system should engage or shut down.
Action: The F9404 Relay Output Module receives the logic signal, de-energizes, and opens the contact, cutting power to a safety-critical device (e.g., fuel shut-off valve).
Ships within 48 hours · Estimated delivery Jul 23 - Jul 28