The Wilkins 34-975XL2SEOS is a reduced pressure principle backflow preventer designed to protect potable water systems from backsiphonage and backpressure hazards.
Key Specifications:
Other Related Variants:
Materials:
The Zurn 34-975XL2SEOS shall be installed horizontally in accordance with manufacturers' instructions and the latest edition of the Uniform Plumbing Code. The assembly shall be mounted at a minimum of 12 inches and a maximum of 30 inches above adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be submerged. Indoor installations shall be supplied with an air gap adapter.
ASSE 1013; cUPC Listed; CSA B64.4; AWWA C511; USC FCCCHR Approved; NSF/ANSI/CAN 61 & 372; UL Classified; C-UL Classified
Features & Benefits:
Q: What is the minimum clearance required for installation?
A: The assembly must be mounted 12 inches minimum and 30 inches maximum above adequate drains with sufficient side clearance for testing and maintenance.
Q: Can this backflow preventer be installed outdoors?
A: Yes, the Zurn 34-975XL2SEOS can be installed outdoors with an optional protective enclosure as shown in the installation diagrams.
Q: What is the hydrostatic test pressure rating?
A: The assembly is rated for a hydrostatic test pressure of 350 PSI, significantly exceeding the maximum working pressure of 175 PSI.
NOTICE: Do not use with water that is unsafe or of unknown quality without adequate disinfection either before or after the system.