Shopping security
The Foxboro P0400YC (FBM02) provides specialized thermal measurement capabilities for the Foxboro I/A Series Distributed Control System (DCS). This 100% Brand New original module interfaces 8 isolated thermocouple and millivolt (mV) signals directly with the system's redundant Fieldbus. It eliminates the need for external transmitters by performing high-precision analog-to-digital conversion internally. Designed for mission-critical process control, the FBM02 (P0400YC) maintains signal integrity in electrically noisy environments, making it an essential component for temperature monitoring in petrochemical refineries, power generation, and chemical processing plants.
Module Type: Thermocouple / Millivolt Input
Part Number: P0400YC (FBM02)
Input Channels: 8 isolated channels
Reference Junction Compensation (CJC): 1 isolated channel utilizing a 100 Ω Platinum RTD
Input Range: -10.5 to +71.41875 mV DC
Isolation: withstands 600 V AC
Communication: Redundant Fieldbus interface
Power Consumption: 8.5 W (Maximum for standard version)
Memory: 16 MB SDRAM / 32 MB Flash
Processor: Single (Standard) or Dual (Fault-tolerant version)
Operating Temperature: 0 to +60 °C (32 to 140 °F)
Dimensions: 2.2 cm × 12.4 cm × 12.6 cm
Weight: 1.5 kg (3.3 lbs)
Integrated Cold Junction Compensation: The P0400YC (FBM02) features dedicated circuitry for Reference Junction Compensation. By using a 100 Ω platinum RTD, the module automatically corrects for ambient temperature fluctuations at the terminal block, ensuring laboratory-grade accuracy in industrial field conditions.
Superior Signal Isolation: Industrial environments often suffer from ground loops and electromagnetic interference. This module provides 600 V AC isolation, which protects the DCS backplane and prevents noise from one thermocouple from corrupting the data on adjacent channels.
Direct Millivolt Processing: The module accepts raw millivolt signals (-10.5 to +71.4 mV), allowing engineers to connect various thermocouple types or specialized low-voltage sensors directly to the system. This reduces the number of intermediate devices and simplifies the overall control architecture.
Fault-Tolerant Reliability: For safety-critical loops, the FBM02 supports dual-processor configurations. This hardware redundancy ensures that temperature monitoring continues without interruption even if a primary processor failure occurs.
What type of RTD does the FBM02 use for CJC?The P0400YC (FBM02) uses a 100 Ω platinum RTD (DIN 43760, Class B) for precise isolated reference junction compensation.
Can the FBM02 be hot-swapped?Yes, the modular design allows for installation or removal from the FBM baseplate without shutting down the entire system, provided you follow standard I/A Series safety protocols.
Does this module support redundancy?The module supports redundant communication via the Fieldbus and can be ordered in a fault-tolerant dual-processor version for maximum system uptime.
Ships within 48 hours · Estimated delivery Aug 1 - Aug 6
US$40
Get nowSign up to your membership to get coupons up to
15%
Get nowOpportunity to enjoy order discount up to 15% off
Top-Converting Item to Boost Your Average Order